Click here to return to the main menu
 







 

Home : Tablet Products : HTS-80PC Automatic Chlorination with Analyzer

The Hammonds Advanced Technology Chlorination System

HTS-80PC Automatic Chlorination with Analyzer

System Description
The HTS-80PC is an automatic, analyzer-controlled version of the standard HTS-80P manual chlorinator. In addition to the basic advanced technology vortex feeder with manual controls, a Hammonds chlorine analyzer provides continuous monitoring of chlorine residual, pH and water temperature. Information from the analyzer is translated to the chlorinator by an integral process controller providing full time precise control of a preset residual.

Hammonds systems utilize state-of-the-art continuous sample water analysis without reagents. The system includes chlorinator, analyzer, complete water sample kit, accessory mounting panel and easy to follow instructions. SCADA-ready controlled deliver both on-site as well as remote monitoring. Hammonds exclusive Tab-Saver® maintains a stable environment for the tablets which extends re-fill intervals to the system. An optional chart recorder completes the package, combining documentation, precision automation and accuracy with the safety and convenience of calcium hypochlorite tablets.

Click here to download Technical Drawings/Manuals >>

Order this system now!

SPECIFICATIONS

  • Entire system pending NSF® Std.61 listing
  • UL® listed electrical control panel
  • SCADA ready
  • Tablet Recommendations: NSF Std. 60 listed solid calcium hypochlorite only
  • Performance: Typical 50 - 2000 GPM wells with PPM residual to 2.0 PPM
  • Chlorine Delivery: 0 - 3.75 pounds per hour.
    Delivery will vary depending on size and manufacture of calcium hypochlorite tablet. Performance based on
  • Solution Metering Pump
    - Type: Balanced diaphragm, positive displacement
    - Performance: 0-3 GPM
  • Chlorine Delivery Controls:
    - Automatic analyzer pacing:
      Analyzer Type: Free chlorine
      No Reagent
      Sample Flow Assembly including:
    • Sample metering flow valve
    • Flow switch for sample valve and DPD measurement
    • PVC tubing for sample collection
    • Automatic pH compensation (optional)
    • Temperature compensation (optional)
    • Chart Recorder (optional)
      8 hour, 24 hour or 7 day, single pen
      Circular Charts, paper
    - Automatic flow pacing: Automatically adjusts pump speed when supplied with 4-20 mA signal from process flow meter
 

 


Automatic Analyzer System

ELECTRICAL SPECIFICATIONS
  • Enclosure: UL® listed NEMA 4X
  • Power Supply: 110 VAC @ 5 amps, actual consumption less than 5 amps
  • Pump Motor: 1/3 hp, variable speed, TEFC, 90 VDC

MATERIALS OF CONSTRUCTION

  • Frame: 1 1/2” x 1 1/2” hot dip galvanized steel
  • Mixing reservoir: NSF® listed 30 gallon - polyethylene (actual used capacity approximately 6 gallons)
  • Tablet Feeder: All components, PVC
  • Solution Tank: NSF® listed 25 gallon polyethylene 12” w x 20 1/2” h x 20” l
  • Piping: (All components NSF® listed)
    - Inlet water supply at bulkhead: 1” Sch. 80 PVC
    - Outlet 1/2" fnpt
    - Circulation to mixing reservoir: 3/4” Sch. 80 PVC
    - Discharge from circulation reservoir to solution tank: 2” Sch. 80 PVC
    - Suction feed to pump: 1” nylon re-enforced PVC clear hose, PVC hose barbs
    - Pump discharge manifold: 1/2” schedule 40, 316 stainless steel rated to 250 PSI
    - Pump discharge manifold to system outlet:
       3/8” nylon re-enforced PVC tubing with PVC hose barbs
    - Relief valve return: Schedule 80 PVC
  • Relief Valve: Sch. 80 PVC
  • Supply Solenoid Valve: PVC
  • Flow limiting valve: PVC
  • Unions/bulkhead fittings: Sch. 80 PVC
  • Pump suction strainer: PVC
  • Pump:
    -- Fluid end: Polypropylene
    -- Valves: 316 S.S.
    -- Elastomers: Viton®
    -- Diaphragm: Viton®
    -- Lube Oil: FDA approved, food grade

OPTIONS

  • Tablet hoist
  • Low tablet alarm
  • Audible alarms
  • Back-up injection pump
  • Liquid phosphate injection
  • 6 foot supply and discharge installation hoses with 1/2” MNPT connections
  • Chart Recorder

MANUALS
Full Product Manual  2.2 mb - Pdf
Schematic Manual  150 kb - Pdf
Parts Manual  278 kb - Pdf
Service Manual  211 kb - Pdf
FlowFit W CCA 250 Flow Assembly
  136 kb - Pdf
Liquisys M CCM 223 / 253 Transmitter
  5.39 Mb - Pdf
CCS 140/141 Chlorine Measuring Cell
145 kb - Pdf


SPECIFICATIONS
HTS 80pc  79 kb - Pdf

TECHNICAL DRAWINGS
General Layout  248 kb - Pdf
Auxiliary Panel
  83 kb - Pdf

Electrical Diagrams  178 kb - Pdf
Fluid Schematic  119 kb - Pdf

Need Adobe Acrobat to read Pdf files? Click here >>